Configuration General tab
- Last UpdatedJul 19, 2024
- 1 minute read
Use the General tab to specify whether the device has feedback (has inputs), can receive commands (has outputs), or both.
|
Editor Option |
Associated Attribute |
Description |
Runtime Access (Supervisory, User, Read-Only, None) |
|---|---|---|---|
|
Enable inputs |
HasFeedback |
If enabled, this discrete device can have feedback (input) from the field. |
None |
|
Historize PV |
PV.Historized |
If enabled, the PV value will be historized. |
None |
|
Force storage period |
PV.ForceStoragePeriod |
See History attributes. |
Supervisory, User |
|
SampleCount |
PV.SampleCount |
See History attributes. |
Supervisory, User |
|
Generate event upon PV change |
PV.LogDataChangeEvent |
If enabled, data change events for the PV will be logged to event history. |
Supervisory, User |
|
Enable outputs |
HasCmd |
If enabled, the discrete device can be commanded to change state. |
None |
|
Historize command |
Cmd.Historized |
If enabled, command changes will be historized. |
None |
|
Force storage period |
Cmd.ForceStoragePeriod |
See History attributes. |
Supervisory, User |
|
SampleCount |
Cmd.SampleCount |
See History attributes. |
Supervisory, User |
|
Enable statistics |
Stats.Enabled |
Used to enable statistics. You can only enable statistics if the object has been configured to have feedback. Statistics provide useful process information calculations on the discrete device being monitored, such as duty cycles and time running utilizations. Statistics also allow you to monitor equipment usage. |
None |