Configure bad value alarms
- Last UpdatedJul 19, 2024
- 1 minute read
Select the Attribute you want to configure in the Attributes List, then click Bad Value Alarm in the configuration pane to add the Bad Value Alarms Feature to the Attribute. Use the following table to configure the Bad Value Alarms feature.
|
Bad Value Alarms Option |
Associated Attribute |
Description |
Runtime Access (Supervisory, User, Read- Only, None) |
|---|---|---|---|
|
Bad Value alarm feature |
Bad.Alarmed |
If enabled, alarms will be triggered when the Attribute has bad data value or bad data quality. |
None |
|
Alarm message |
Bad.DescAttrName |
The name of the attribute (within the same object) to be used as the alarm message. The attribute you specify must be of type String or InternationalizedString, with a maximum string length of 329 characters. If no attribute is specified, the Attribute description is used as the alarm message. Click the ellipse button to access the Attribute Browser. |
Supervisory, User |
|
Priority |
Bad.Priority |
The value for the urgency of the alarm. Valid values are 1 through 999, with 1 being the most urgent. |
Supervisory, User |