Object configuration Engine History tab
- Last UpdatedJul 19, 2024
- 2 minute read
Use the Engine History tab to enable historization for various status counts that are generated by the ViewEngine object.
|
Editor Option |
Associated Attribute |
Description |
Runtime Access (Supervisory, User, Read-Only, None) |
|---|---|---|---|
|
Historize external reference count |
Engine.ExternalReferenceCnt.Historized |
If enabled, the system will historize the number of registered external references. |
None |
|
Historize external reference count unbound |
Engine.ExternalReferenceCntUnbound.Historized |
If enabled, the system will historize the number of registered external references that are unbound. |
None |
|
Historize issued external gets count |
Engine.IssuedExternalGetsCnt.Historized |
If enabled, the system will historize the number of off-engine gets (initiated from AutomationObjects on this object). |
None |
|
Historize issued external sets count |
Engine.IssuedExternalSetsCnt.Historized |
If enabled, the system will historize the number of off-engine sets (initiated from AutomationObjects on this object). |
None |
|
Historize issued internal gets count |
Engine.IssuedInternalGetsCnt.Historized |
If enabled, the system will historize the number of on-engine gets (initiated from AutomationObjects on this object). |
None |
|
Historize issued internal sets count |
Engine.IssuedInternalSetsCnt.Historized |
If enabled, the system will historize the number of on-engine sets (initiated from AutomationObjects on this object). |
None |
|
Historize received external gets count |
Engine.RcvdExternalGetsCnt.Historized |
If enabled, the system will historize the number of incoming external gets (received from other engine objects that do not exist on this object). |
None |
|
Historize received external sets count |
Engine.RcvdExternalSetsCnt.Historized |
If enabled, the system will historize the number of incoming external sets (received from other engine objects that do not exist on this object). |
None |
|
Historize alarms throttled flag |
Engine.AlarmsThrottled.Historized |
If enabled, the system will historize the number of alarms that have been throttled in the prior scan. The limit for the number of alarms per second that can be raised by this object before throttling occurs is set using the alarm throttle limit. |
None |
|
Historize publish packets received count |
Engine.PublishPacketsRcvdCnt.Historized |
If enabled, the system will historize the number of publish packets received on this engine from other engines. |
None |
|
Historize publish packets sent count |
Engine.PublishPacketsSentCnt.Historized |
If enabled, the system will historize the number of publish packets sent from this engine to other engines. |
None |
|
Force storage period |
<AttributeName>.ForceStoragePeriod |
See History attributes. |
Supervisory, User |
|
Value deadband |
<AttributeName>.Deadband |
See History attributes. |
Supervisory, User |
|
Trend high |
<AttributeName>.TrendHi |
See History attributes. |
Supervisory, User |
|
Trend low |
<AttributeName>.TrendLo |
See History attributes. |
Supervisory, User |
|
Interpolation Type |
<AttributeName>.InterpolationType |
See History attributes. |
Supervisory, User |
|
Sample Count |
<AttributeName>.SampleCount |
See History attributes. |
Supervisory, User |
|
Rollover Value |
<AttributeName>.RolloverValue |
See History attributes. |
Supervisory, User |
|
Enable Swinging Door |
<AttributeName>.EnableSwingingDoor |
See History attributes. |
Supervisory, User |
|
Rate DeadBand |
<AttributeName>.RateDeadBand |
See History attributes. |
Supervisory, User |