Configure deviation alarms

  • Last UpdatedJul 19, 2024
  • 2 minute read

Select the Attribute you want to configure in the Attributes List, then click Deviation Alarms in the configuration pane to add the Deviation Alarms Feature to the Attribute. Use the following table to configure the Deviation Alarms feature.

Deviation Alarms Option

Associated Attribute

Description

Runtime Access (Supervisory, User, Read- Only, None)

Deviation alarms feature

DeviationAlarmed

If enabled, alarms will be triggered when the Attribute level deviates from a target value by a configured amount.

None

Minor

Dev.Minor.Alarmed

If enabled, an alarm will be triggered when the Attribute value reaches the minor deviation tolerance.

None

Minor - Tolerance

Dev.Minor.Tolerance

The minor deviation tolerance that the Attribute value must exceed to trigger an alarm.

Supervisory, User

Minor - Priority

Dev.Minor.Priority

The value for the urgency of the alarm. Valid values are 1 through 999, with 1 being the most urgent.

Supervisory, User

Minor - Alarm message

Dev.Minor.DescAttrName

The name of the attribute (within the same object) to be used as the alarm message. The attribute you specify must be of type String or InternationalizedString, with a maximum string length of 329 characters. If no attribute is specified, the Attribute description is used as the alarm message.

Click the ellipse button to access the Attribute Browser.

Supervisory, User

Major

Dev.Major.Alarmed

If enabled, an alarm will be triggered when the Attribute value reaches the major deviation tolerance.

None

Major - Tolerance

Dev.Major.Tolerance

The major tolerance that the Attribute value must exceed to trigger an alarm.

Supervisory, User

Major - Priority

Dev.Major.Priority

The value for the urgency of the alarm. Valid values are 1 through 999, with 1 being the most urgent.

Supervisory, User

Major - Alarm message

Dev.Major.DescAttrName

The name of the attribute (within the same object) to be used as the alarm message. The attribute you specify must be of type String or InternationalizedString, with a maximum string length of 329 characters. If no attribute is specified, the Attribute description is used as the alarm message.

Click the ellipse button to access the Attribute Browser.

Supervisory, User

Target

Dev.Target

Sets the Attribute target setpoint value for the deviation calculation.

Supervisory, User

Deviation deadband

Dev.Deadband

The amount the Attribute value must drop (measured in engineering units) below any of the deviation limits before the respective condition is set to FALSE.

Supervisory, User

Settling period

Dev.SettlingPeriod

The time, in seconds, allowed for the Attribute value to return within the allowable range after a Target change is made before the deviation alarm is triggered. (A deviation alarm cannot occur again until the alarm clears.) The value you specify will be converted to the following format: days hh:mm:ss.fffffff.

Supervisory, User