Limit alarms attributes

  • Last UpdatedJul 19, 2024
  • 2 minute read

If Enable limit alarms is enabled, then the following additional limit alarm-related attributes become available.

Editor Option

Associated Attribute

Description

Runtime Access

Enable limit alarms

LimitAlarmed

If enabled, alarms will be triggered when the value reaches configured alarm limits.

None

HiHi

HiHi.Alarmed

If enabled, an alarm will be triggered when the Field Attribute value reaches the HiHi limit.

None

HiHi - Limit

HiHi.Limit

The HiHi limit that the Field Attribute value must exceed to trigger an alarm.

Supervisory, User

HiHi - Priority

HiHi.Priority

See Alarm field attributes.

Supervisory, User

HiHi - Alarm message

HiHi.DescAttrName

See Alarm field attributes. Click the ellipse button to access the Attribute Browser.

Supervisory, User

Hi

Hi.Alarmed

If enabled, an alarm will be triggered when the Field Attribute value reaches the Hi limit.

None

Hi - Limit

Hi.Limit

The Hi limit that the Field Attribute value must exceed to trigger an alarm.

Supervisory, User

Hi - Priority

Hi.Priority

See Alarm field attributes.

Supervisory, User

Hi - Alarm message

Hi.DescAttrName

See Alarm field attributes. Click the ellipse button to access the Attribute Browser.

Supervisory, User

Lo

Lo.Alarmed

If enabled, an alarm will be triggered when the Field Attribute value reaches the Lo limit.

None

Lo - Limit

Lo.Limit

The Lo limit that the Field Attribute value must exceed to trigger an alarm.

Supervisory, User

Lo - Priority

Lo.Priority

See Alarm field attributes.

Supervisory, User

Lo - Alarm message

Lo.DescAttrName

See Alarm field attributes. Click the ellipse button to access the Attribute Browser.

Supervisory, User

LoLo

LoLo.Alarmed

If enabled, an alarm will be triggered when the Field Attribute value reaches the LoLo limit.

None

LoLo - Limit

LoLo.Limit

The LoLo limit that the Field Attribute must exceed to trigger an alarm.

Supervisory, User

LoLo - Priority

LoLo.Priority

See Alarm field attributes.

Supervisory, User

LoLo - Alarm message

LoLo.DescAttrName

See Alarm field attributes. Click the ellipse button to access the Attribute Browser.

Supervisory, User

Alarm deadband

LimitAlarm.ValueDeadband

The amount, in engineering units, that the Field Attribute value must drop below either the HiHi limit or Hi limit, or increase above either the LoLo limit or Lo limit before an alarm is triggered.

Supervisory, User

Time deadband

LimitAlarm.TimeDeadband

The time, in seconds, that must elapse after the Field Attribute value exceeds an alarm limit before the alarm is triggered.

Supervisory, User