Runtime object attributes
- Last UpdatedJul 19, 2024
- 1 minute read
The following section describes the runtime only attributes for the object.
Note: Configurable runtime attributes are described in the configuration sections. For more information, see Object configuration.
For a list of common attributes, click Attributes Help in the Help file header.
|
Attribute |
Description |
Runtime Access (Supervisory, User, Read-Only, None) |
|---|---|---|
|
AlarmDSCnt |
The total number of disabled and silenced alarms in the object. Sub-areas or sub-notification-distributors are not included. For extra quality information, see Quality handling. |
Read-Only |
|
AlarmDSCntTotal |
The total number of disabled and silenced alarms in the Area object, including alarms in sub-areas or sub-notification-distributors. For extra quality information, see Quality handling. |
Read-Only |
|
AlarmOnCnt |
The number of active alarms in the distributor. Does not include sub-areas or sub-notification-distributors. For extra quality information, see Quality handling. |
Read-Only |
|
AlarmOnCntTotal |
The total number of active alarms in the Area object, including alarms in sub-areas or sub-notification-distributors. For extra quality information, see Quality handling. |
Read-Only |
|
AlarmUnAckedCnt |
The number of unacknowledged alarms in the distributor (including unacknowledged return-to-normals). Does not include sub-areas or sub-notification-distributors. For extra quality information, see Quality handling. |
Read-Only |
|
AlarmUnAckedCntTotal |
The total number of unacknowledged alarms and return-to-normals in the Area object, including alarms for sub-areas or sub-notification-distributors. For extra quality information, see Quality handling. |
Read-Only |