Target deviation alarm attributes

  • Last UpdatedJul 19, 2024
  • 2 minute read

If Enable target deviation alarms is enabled, then the following additional scaling alarm-related attributes become available.

Editor Option

Associated Attribute

Description

Runtime Access

Enable target deviation alarms

DeviationAlarmed

If enabled, alarms will be triggered for when the Field Attribute level deviates from a target value by a configured amount.

None

Minor

Dev.Minor.Alarmed

If enabled, an alarm will be triggered when the Field Attribute value reaches the minor deviation tolerance.

None

Minor - Tolerance

Dev.Minor.Tolerance

The minor deviation tolerance that the Field Attribute value must exceed to trigger an alarm.

Supervisory, User

Minor - Priority

Dev.Minor.Priority

See Alarm field attributes.

Supervisory, User

Minor - Alarm message

Dev.Minor.DescAttrName

See Alarm field attributes. Click the ellipse button to access the Attribute Browser.

Supervisory, User

Major

Dev.Major.Alarmed

If enabled, an alarm will be triggered when the Field Attribute value reaches the major deviation tolerance.

None

Major - Tolerance

Dev.Major.Tolerance

The major deviation tolerance that the Field Attribute value must exceed to trigger an alarm.

Supervisory, User

Major - Priority

Dev.Major.Priority

See Alarm field attributes.

Supervisory, User

Major - Alarm message

Dev.Major.DescAttrName

See Alarm field attributes. Click the ellipse button to access the Attribute Browser.

Supervisory, User

Target

Dev.Target

Sets the Field Attribute target setpoint value for deviation calculation.

Supervisory, User

Deviation deadband

Dev.Deadband

The amount the Field Attribute value must drop (measured in engineering units) below any of the deviation limits before the respective condition is set to FALSE.

Supervisory, User

Settling period

Dev.SettlingPeriod

The time, in seconds, allowed for the Field Attribute value to return within allowable range after a Target change is made before the deviation alarm is triggered. (A deviation alarm cannot occur again until the alarm clears.) The value you specify will be converted to the following format: days hh:mm:ss.fffffff.

Supervisory, User