AVEVA™ Operations Management Interface

About feature and runtime behavior

  • Last UpdatedJul 17, 2024
  • 1 minute read

The following information describes Feature and Attribute runtime behavior.

Feature

Behavior

Input processing

(when Input is configured)

  • Get input value and set Attribute value.

  • If the input source supports a time stamp, the PV is updated with the value, time stamp, and quality (VTQ) of the source attribute. If the input source does not support a time stamp, the value and quality of the source attribute is used, and a time stamp of the current time is generated for any change in source attribute's value or quality. If the quality of the Value attribute changes, the time stamp is updated to the current time.

  • Perform scaling, if enabled. The Attribute is updated with a new value if the difference between the new value and the old value exceeds the Deadband.changes, the time stamp is updated to the current time.

  • If state labels are configured, map Attribute value to the corresponding configured state and set [Attribute].Msg.

  • If alarming features are enabled, then calculate the alarms.

Statistics processing

(when Statistics are enabled)

  • Calculate the durations for the current time and total time that the Attribute was in the State0, State1, and Passive states.

  • If the Attribute value has just changed to a new state, increment the counter for the new Attribute value state.

  • Detect the duration alarms for the State0 state total duration, and State1 state total duration.

Alarm processing

  • Get the input value and compare with the ActiveAlarmState.

  • If the value matches with the ActiveAlarmState, then set the Alarm.Condition to TRUE.

  • If the value does not match, then clear Alarm.Condition.