Location4
- Last UpdatedApr 03, 2023
- 1 minute read
For interfaces that support scan-based collection of data, Location4 defines the scan class for the PI point. The scan class determines the frequency at which input points are scanned for new values. In addition, points in the first scan class will be configured for exception data collection. Points in all other scan classes will be configured to collect archive data.
Specify scan frequency and optional offset using the following format:
HH:MM:SS.##,HH:MM:SS.##