Overriding I/O Points

  • Last UpdatedJun 30, 2020
  • 2 minute read

In the following procedure, we override the current value of the tank level with a false value and watch the control system respond.

  1. On the main window, click the Tools menu and select Cross Reference Table, or click the appropriate icon () and click OK in the Cross Reference Filter.

  2. Under the Analog tab, highlight the row containing the VTL2.OP command in the To Symbol.

    Embedded Image (65% Scaling) (LIVE)

  3. In the XRef Editor window toolbar, click the Override button.

  4. Set the Mature Value to 1.

  5. Click the Activate button. The demand to VTL2 increases to correct the supposed error in tank level.

  6. Click the Save button located next to Activate (we will use the saved malfunction in an upcoming section).

  7. In the Select a System dialog box, select Tank Level Control and click OK.

  8. Click the Deactivate button to discontinue override and close the Malfunction popup.