Defects / Issues Resolved in v4.1 Release
- Last UpdatedNov 09, 2020
- 1 minute read
|
CR |
Feature |
Defect or Issue |
|
TFS #508188 |
TRISIM does not accept unsigned 32-bit integer values |
TRISIM expected 32-bit integer values transferred through simulation cross referencing to be signed values (-2,147,483,648 to 2,147,483,647). Several SCP block outputs would produce unsigned integer values (0 to 4,294,967,295). TRISIM input blocks would only see a range of 0 to 2,147,483,647. A new UOM conversion function converts an unsigned integer to a signed integer. For more information, see "Cross Referencing Unsigned 32-bit Integers" in the AVEVA Simulation for Triconex Systems – User Guide. |