PCS and MGC issues
- Last UpdatedDec 19, 2024
- 2 minute read
PCS: Platform Common Services
MGC: Multi-Galaxy Communication
|
Issue Number |
Description |
|
IMS 3456786 |
After upgrading to PCS 8.1.2 on a node that has both System Platform 2023 R2 or 2023 R2 SP1 and Recipe Management 2023 R2, the RMPEventSvc service does not start and you are not able to view Recipe Management events in the OCMC Logger. The Logger also shows continuous warnings related to the PCS agent. Workaround: On the server running System Platform and Recipe Management 2023 R2, modify the file aaEventsEventService.aaSDEF by adding the <LaunchAssembly> property. Full path of the aaEventsEventService.aaSDEF file:
|
|
IMS 2829309 |
If you are using the connected experience for security and you close the browser window where you signed in when starting an OMI ViewApp, you may see one of these symptoms when signing out of the ViewApp:
|
|
IMS 2658043 |
In an installation which uses workgroups and has MultiCast-DNS enabled, upgrading from an earlier version to PCS 8.0 (for example, during an upgrade to System Platform 2023 R2) causes an issue with the PCS certificate. This causes secure communication with the SMS to fail. The SMS falls back to using non-secure communication. This causes error messages to be written continuously to the logger on all remote nodes. Workaround: Perform the following procedure on all nodes, including the SMS node:
|
|
IMS 1586624 |
The logger will repeatedly display error/exception messages from the "view" component if a multi-galaxy pairing is broken for any reason, and then an InTouch HMI Managed ViewApp is launched that contains cross-references to tags in another galaxy. Workaround: Since the exceptions are caused by the broken galaxy pairing, simply pair the galaxies again. The exceptions will no longer be logged. |