I/O baselines

  • Last UpdatedAug 13, 2025
  • 1 minute read

This topology type was tested for integration purposes in a lab environment and uses simulated I/O for data generation. "Real" I/O results (from PLCs) are included in the following section as a subset of this test configuration.

Platforms - Visualization nodes

10

Platforms - AutomationObject Servers

20

Platforms - Galaxy Repository Server

1

IndustrialSQL Server Historian Server

5

Object Instances per Galaxy

50,000

Object Instances per Server Platform

2500

I/O per Galaxy

1,100,000

I/O Points per Server Platform

55,000

I/O Change Rate

3% I/O points change every scan

Alarm Rate

1% of I/O points per scan

History stores

7000 changes/sec

The following results table contains simulated and real I/O values:

Physical Memory Use (MB)

Page File Usage (MB)

%CPU Average

%Network (RMC)

%Network (Primary)

Normal Engine (simulated I/O)

871

652

21-29

N/A

0.01

Redundant Engine (simulated I/O)

908

791

22-30

0.12

0.01

IT Platform (TSE)

759

707

23

N/A

0.01

Load Sharing (simulated I/O)

770

930

27-30

0.24

0.01

Redundant Engine (Real I/O)

913

782

55

0.15

0.03

  • Primary Network line speed: 1 Gbps

  • RMC Network line speed: 1Mbps

    Note: Attribute tuning for Redundant AppEngines is described on "Tuning Redundant Engine Attributes" on page 87.