The following issues may be seen when using long instance names.
|
Issue |
Description |
|
IMS 3533007 |
The ITAlarmProvider component will log warnings while generating alarms and events, if the total length used for ObjectName, AttributeName, Attribute Description and Alarm comments exceed 450 characters. This is due to a limitation in the AlarmManager component. This limitation will be fixed in a future release. |
|
IMS 3509408 |
Data cannot be read from or written to the OPC UA Service when long object and attribute names are used. The total reference string (object name plus attribute name) cannot exceed 254 characters. If the reference string exceeds 254 characters, you will see errors generated from the aaCALWrapper.exe process and WWCLINTF component. |
|
Redundant Telemetry Server issue |
In a Redundant Telemetry Server deployment using PCS connectivity to Application Server, failover from the primary Telemetry Server to secondary Telemetry Server is not instantaneous and may take several seconds to complete. During this time, loss of data may occur. |