The following specification was implemented for single-node tests:

  • 1000 I/O points with update rate 1 sec - make sure these I/O points are distributed among all different data types and are distributed between the DA Servers and legacy I/O Servers as well as be sure to use all three communication protocols (S/L, OPC and DDE).

  • 50% floats, 25% bools, 10% strings, 15% integers.

  • 10% changing I/O points - 100 items were updated every second. However, the server scanned for 1000 items per second

  • 10% I/O points Historized - maintain the same ratio for various data types.

  • (Maximum) 3 AppEngines - Approximately 70 objects per engine.

  • (Maximum) 200 AppObjects - 5 I/O points-per-object.

  • Alarm rate: 2 Alarms per second.