Data Archive Administration

Filtercode

  • Last UpdatedOct 02, 2024
  • 1 minute read

The Filtercode indicates the time constant of a first-order filter used to smooth incoming data. While it does impact the compressed data, it does not affect exception reporting.

We recommend not altering incoming data by leaving this code at its default value of 0. The other options are:

Code

Time Constant (Seconds)

1

10

2

60

3

120

4

600