Data Archive Administration

Subsystem health checks (RPC resolver error messages)

Subsystem health checks (RPC resolver error messages)

  • Last UpdatedOct 02, 2024
  • 1 minute read

Every few minutes, pinetmgr sends a health check message to each of the Data Archive subsystems. If pinetmgr does not receive a response within a given amount of time, it generates the following message and the subsystem (RPC resolver) is marked offline:

>> Deleting connection: pisnapss, Subsystem Healthcheck failed.

If an RPC is made to a subsystem that is marked offline, you will see this message:

[–10733] PINET: RPC Resolver is Off–Line

The output will include details if only the first part of a message was retrieved. In this example, the message contains the message length. However, a timeout occurred when pinetmgr attempted to retrieve the rest of the message:

>> Deleting connection: pisnapss, Connection lost(1),
[-10731] PINET: incomplete message