Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Operations Management Interface

Resolved issues - AVEVA OMI 2023 R2 Patch 01

  • Last UpdatedNov 01, 2024
  • 2 minute read

This table lists AVEVA OMI issues resolved by Patch 01. Some issues that have been fixed in this release may not be listed.

Original Issue

Related Issues

Case/SR Number

Description

IMS 839617

960372244

If you performed these steps:

  1. Created a layout and exported it to a package (.aaPKG) file.

  2. Imported the package file to a galaxy that used a different regional setting--for example, if the original GR node was set to Dutch(Belgium) and the new GR node was set to English.

  3. Tried to open the layout in the IDE.

    The layout would not open and you would see a message similar to this in the log: System: 221; 0; 0; 0 is not a valid value for Int32.

IMS 2507960

None

Faceplate popup graphics opened using ShowGraphic appeared at the top-right corner of the window instead of in the center.

IMS 2623094

960329675

Certain OMI ViewApps would sometimes freeze for five to ten seconds while a user was browsing object attributes.

IMS 2865278

960346739

When using Multi-Galaxy Communication, running an OMI ViewApp that retrieved data from another galaxy failed if Remote Desktop Services was installed and enabled on the node where the ViewApp was running. A warning was written to the log.

IMS 3023269

960368607

If more than 30 users were connected to OMI using RDP sessions, the following warning messsage was logged when a user closed an application: Release of global semaphore for the view application <app_name> failed. Deploy/undeploy operation may be blocked.

IMS 3031945

960379257

Addressed issues with tooltip text wrapping and combo box size when viewing OMI VIewApps in the OMI web client.

IMS 3032032

960379261

In the OMI web client, when interaction animation was applied to both an outer object and an inner object, the animation for the outer object overlapped the animation for the inner object. This could make it impossible to select the inner object.

IMS 3037177

960383529

Changing the background color for the ScreenCaptureAndPrint App at design time did not change the color when the ViewApp was opened in runtime.

IMS 3040067

960383669

When opening a faceplate graphic in a popup in the OMI web client, the popup window included a minimize button.

IMS 3046276

None

Changes made to graphics contained in a ViewApp were not always reflected at runtime after the ViewApp was redeployed.

IMS 3060440

None

After migrating a galaxy from 2023 Patch 02 to 2023R2, an exception could occur when previewing a ViewApp. A warning was written to the logger:

IMS 3060445

960385565

Content displayed through the ShowContent script in a tabbed multi-content layout pane with autofill enabled was not cleared when you changed the navigation node.

IMS 3061706

960386804

When a custom property was assigned with System.DateTime.Now and the SetCustomPropertyValue script was simultaneously called on the same custom property, it caused a memory leak. Eventually, this caused the viewer to crash with a SystemOutOfMemoryException error.

IMS 3199437

960392885

Switching between navigation items in the NavTree app in a ViewApp could caused the ollowing message in the log: System.ArgumentNullException: Value cannot be null.