Issue Number

Description

TFS 1342283

If you attempt to upgrade a computer to System Platform 2023 R2 SP1 from System Platform 2020, and AVEVA Edge 2020 is installed on the same computer, an error message may be displayed that warns of an incompatibility. This will occur during the upgrade if certain registry values are incorrect, and the upgrade installation will be blocked.

Workaround: Use regedit to enter the correct registry values.

Location: HKEY_LOCAL_MACHINE\SOFTWARE\WOW6432Node\ArchestrA\Framework

  1. Change the value of InstallPath to C:\Program Files (x86)\ArchestrA\Framework\ (add the final backslash character)

  2. Change the value of TargetInstallPath to C:\Program Files (x86)\ArchestrA\ (add “ArchestrA\”)