Read/write status codes for direct communication drivers
- Last UpdatedOct 29, 2026
- 7 minute read
This is a list of common status codes that are generated by communication drivers during read/write operations.
|
Status Code |
Description |
Possible Causes |
Procedure To Solve |
|---|---|---|---|
|
0 |
OK |
Communicating without error. |
None required. |
|
-1 |
Invalid serial port |
|
|
|
-2 |
Invalid baud rate |
The selected baud rate is invalid. |
Select a baud rate in the valid range. |
|
-3 |
Invalid number of bits |
The selected number of bits for the serial port is invalid. |
Select a number of bits in the valid range. |
|
-4 |
Invalid number of stop bits |
The selected number of stop bits for the serial port is invalid. |
Select a number of stop bits in the valid range. |
|
-5 |
Invalid parity |
The selected parity for the serial port is invalid. |
Select a parity in the valid range. |
|
-6 |
Invalid IRQ |
The selected IRQ for the serial port is invalid. |
Select an IRQ in the valid range. |
|
-7 |
Serial port already in use |
The selected port is being used by other process. |
Choose another serial port for communication. |
|
-8 |
Invalid buffer size |
The buffer size entered is not allowed. |
Check the documentation for allowed buffer sizes. |
|
-9 |
Memory not enough |
Out of memory in the system. |
Close other processes that may be consuming memory. |
|
-10 |
Tx buffer empty |
The CE device was not able to write the message on the serial port. |
Check if the serial port is valid and accessible. |
|
-11 |
Tx buffer full |
The TX buffer has more data than allowed. |
Increase the TX buffer size in driver settings. |
|
-12 |
Rx buffer empty |
No data was received. |
Check if the serial port is valid and the device is sending data. |
|
-13 |
Rx buffer full |
The RX buffer has more data than allowed. |
Increase the RX buffer size in driver settings. |
|
-14 |
Timeout waiting CTS |
The CTS was not received in the expected time. |
|
|
-15 |
Timeout waiting for message to start |
|
|
|
-16 |
Timeout waiting for message to finish |
The message took too long to be received as completed. |
Increase the timeout for End message in driver settings. |
|
-17 |
Timout between rx character |
The time between characters is too long. |
Increase the Interval between char in driver settings. |
|
-18 |
Timout between tx character |
|
Check the serial port settings. Increase the Interval between char in driver settings. |
|
-19 |
No carrier detected |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-20 |
No DSR detected |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-21 |
Could not find a 8250 in address |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-22 |
Tx line is busy |
The TX buffer is full and unable to write to the serial buffer. |
|
|
-23 |
User abort |
User has aborted the request. |
Retry the request without aborting it. |
|
-24 |
Function not supported |
Serial port received an unsupported function. |
Check the serial port configuration and status. |
|
-25 |
Overrun |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-26 |
Parity |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-27 |
Overrun and parity |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-28 |
Framing |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-29 |
Framing and overrun |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-30 |
Framing and parity |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-31 |
Framing, overrun, and parity |
Invalid serial port configuration or hardware fault. |
Check the serial port configuration and status. |
|
-32 |
Timeout waiting for a tx message to finish |
The message could not be sent completely or partially. |
|
|
-33 |
Invalid driver configuration file |
The driver configuration file (drivername.ini) is missing or corrupt. |
Reinstall the driver. |
|
-34 |
Invalid address |
The specified address is invalid or out of range. |
Check the supported range of addresses described in this document, and then correct the address. |
|
-35 |
Driver API not initialized |
The driver library did not initialize. |
Contact technical support. |
|
-36 |
Invalid data type |
The specified data type is invalid or out of range. |
Check the supported data types described in this document, and then correct the data type. |
|
-37 |
Invalid header |
The specified header in the driver worksheet is invalid or out of range. |
Check the supported range of headers described in this document, and then correct the header. |
|
-38 |
Invalid station |
The specified station in the driver worksheet is invalid or out of range. |
Check the supported station formats and parameters described in this document, and then correct the station. |
|
-39 |
Invalid block size |
Worksheet is configured with a range of addresses greater than the maximum block size. |
Check the maximum block size number of registers described in this document, and then configure your driver worksheet to stay within that limit. Keep in mind that you can create additional worksheets. Note: If you receive this error from a Main Driver Sheet or Tag Integration configuration, please contact Technical Support. |
|
-40 |
Invalid bit write |
Writing to a bit using the attempted action is not supported. |
|
|
-42 |
Invalid bit number |
The bit number specified in the address is invalid. The limit for the bit number depends on the registry type. |
Check the addresses to see if there are bit numbers configured outside the valid range for the registry. |
|
-43 |
Invalid byte number |
The byte number specified in the address is invalid. The limit for the byte number depends on the registry type. |
Check the addresses to see if there are byte numbers configured outside the valid range for the registry. |
|
-44 |
Invalid byte write |
Writing to a byte using the attempted action is not supported. |
The byte is read-only or inaccessible. |
|
-45 |
Invalid string size |
The string is more than 1024 characters. |
Modify the addresses that have string data type to be less than 1024 characters. |
|
-50 |
Invalid modem |
The selected modem name is invalid. |
Select a valid modem name in driver settings. |
|
-51 |
Error initializing TCP |
The TCP library is not available for serial encapsulation. |
Reinstall the driver. |
|
-52 |
Error listening to port |
The port selected in serial encapsulation settings is not available. |
|
|
-53 |
Error initializing UDP |
The UDP library is not available for serial encapsulation. |
Reinstall the driver. |
|
-54 |
Error sending data packet (TCP or UDP) |
The TCP/UDP library was not able to send the packet. |
Check the serial encapsulation settings. |
|
-55 |
Error not connected |
Modem is not connected. |
|
|
-56 |
Invalid connection handle |
The connection is no longer valid. |
Please contact Technical Support. |
|
-57 |
Message could not be sent |
The socket was unable to send the TCP or UDP message. |
|
|
-58 |
TCP/IP could not send all bytes |
The TCP/IP stack was not able to send all bytes to destination. |
|
|
-60 |
Error to establish TCP/IP connection |
Error while establishing a TCP/IP connection with the unit device. Possibly incorrect IP address or port number in the specified station. |
|
|
-61 |
TCP/IP socket error |
The TCP/IP connection has been closed by the device. |
Confirm that the device is active and accessible. Try to ping the address. |
|
-62 |
UDP/IP receive call returned error |
The UDP socket is in error. |
|
|
-63 |
UDP/IP error initializing |
The UDP socket initialization failed. |
Confirm that the operating system supports UDP sockets. |
|
-64 |
UDP/IP receive call returned error |
The UDP socket is in error. |
|
|
-65 |
UDP/IP bind error, port number may already be in use |
The driver was not able to bind the UDP port. |
|
|
-66 |
Unlicensed driver |
Your runtime license does not allow you to run this driver. |
Contact your software distributor. |
Notes