Configure the communication driver

  • Last UpdatedOct 29, 2026
  • 3 minute read

This part of the tutorial shows how to select and configure a driver to communicate with an external I/O device.

  1. In the Project Explorer, select the Comm tab.

  2. Right-click the Drivers folder, and the select Add/Remove Drivers on the shortcut menu.

    The Communication Drivers dialog is displayed.

  3. Highlight a driver in the Available drivers list, and then choose Select.

    For this tutorial, select MODBU.

    The driver is moved to the Selected drivers list.

    Communication Drivers dialog

  4. Select OK.

    The Communication Drivers dialog is closed, and the driver is added to the Drivers folder in the Project Explorer.

  5. In the Project Explorer, right-click the MODBU folder, and then select Settings on the shortcut menu.

    Project Explorer with MODBU folder selected

    The Communication Settings dialog is displayed.

    Communication Settings dialog for MODBU driver

  6. Configure the communication settings as needed for the target device. For this tutorial, you can accept the default settings.

    For more information about a specific driver, select Communication Drivers on the Help tab of the ribbon.

  7. Click OK to close the dialog.

  8. In the Project Explorer, right-click the MODBU folder and then select Insert on the shortcut menu.

    A new driver worksheet named MODBU001.drv is created and opened for editing.

  9. Configure the worksheet header:

    1. In the Description box, type Tutorial Modbus.

      This setting is for documentation only; it does not affect the project during run time.

    2. In the Enable Read When Idle box, type 1.

      This setting is a trigger that takes a Boolean value. A value of 1 โ€” either entered manually as above or evaluated from a tag/expression โ€” forces your project to continue reading tag values from the target device even when there are no changes in value.

    3. In the Enable Write On Tag Change box, type 1.

      This setting is also a trigger. A value of 1 forces your project to write tag values to the target device only when those values change, rather than continuously. This improves runtime performance.

    4. In the Station box, type 1.

      This indicates the I/O device number to be accessed by this driver. Typically, the PLC is specified as Device #1.

    5. In the Header box, type 4X:0.

      Each driver has a specific format. The format for the MODBU driver is:

      register_type:initial_offset

    Register Type

    Description

    0X

    Coil Status

    1X

    Input Status

    3X

    Input Register

    4X

    Holding Register

    ID

    Unit ID Number

    Completed worksheet header

  10. In the worksheet body, enter the tags and their associated device addresses โ€” for each tag:

    1. In the Tag Name field, type the name of the project tag.

    2. In the Address field, type the value to be added to the header to form the complete device address.

    Tag Name

    Address

    Complete Device Address

    Level[1]

    1

    4X:1 (Holding Register 1)

    Level[2]

    2

    4X:2 (Holding Register 2)

    Level[3]

    3

    4X:3 (Holding Register 3)

    Completed worksheet body

  11. Go to File, and then select Save.

  12. When prompted to choose the driver sheet number, type 1 and then select OK.