TagsDBBeginEdit is a built-in function that locks the tags database for editing during run time. You must call this function before you call any other Tags Database functions to add or remove project tags or set tag properties.

Function

Group

Execution

String Exp.

Windows

Windows Embedded

IoT View

Thin Clients

Mobile Access

TagsDBBeginEdit

Tags Database

Synchronous

No

Supported (see Notes below)

Not supported

Not supported

Not supported

Not supported

Syntax

TagsDBBeginEdit()

TagsDBBeginEdit ( )

This function has no parameters.

Returned value

This function returns one of the following possible values:

Value

Description

0

Function executed successfully.

-1

Project runtime is busy; another function is editing the tags database. Try again later.

-2

Invalid number of parameters.

-3

Project runtime is busy; an Alarm or Trend task is using the tags database. Try again later.

Notes

The following restrictions apply to the execution of this function:

  • The function can only be executed on the project server — it cannot be called by a Graphics Script, Screen Script, or Command animation running on a project client; and

  • The function TagsDBEndEdit must be executed when the editing is finished, in order to release the tags database and resume normal runtime operations.

For more information about the Tags Database functions and examples of how to use them, see Using TagsDB functions to edit the tags database during run time.

Please note this function has a persistent effect, which means that if you call the function to lock the tags database during run time and then stop the project, the database will remain locked and you will not be able to manually edit it.

Restarting the project may or may not unlock the database, depending on how you designed your project and which function call locked the database in the first place. As such, while the project is stopped, you should use the Watch window to manually call the function TagsDBEndEdit. When it is successfully executed, you can safely restart the project.