Edge HMI

TagsDBSetAlarm

  • Last UpdatedOct 29, 2026
  • 3 minute read

TagsDBSetAlarm is a built-in function that sets the value of a property of an alarm condition during run time.

Function

Group

Execution

String Exp.

Windows

Windows Embedded

IoT View

Thin Clients

Mobile Access

TagsDBSetAlarm

Tags Database

Synchronous

No

Supported (see Notes below)

Not supported

Not supported

Not supported

Not supported

Syntax

TagsDBSetAlarm(strTagName,numAlarmType,numProperty,strOrNumVal)

TagsDBSetAlarm ( strTagName , { numAlarmType | -1 | 1 | 2 | 4 | 8 | 16 | 32 | 64 } , { numProperty | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 } ,strOrNumVal)

strTagName

The name of the project tag on which the alarm property will be set.

Tip: To set other properties on project tags, use the function TagsDBSetTagProperty.

numAlarmType

The type of alarm on the specified project tag, identified by one of the following values:

Value

Alarm Type

-1

General properties that apply to all alarm types on the specified project tag

1

HiHi

2

Hi

4

Lo

8

LoLo

16

Rate

32

DeviationP

64

DeviationM

numProperty

The alarm property that you want to set.

When setting a property of a specific alarm type (that is, if numAlarmType is greater than 0), the property is identified by one of the following values:

Value

Property

Data Type

0

Limit value

Real

1

Message

String

2

Alarm group (or worksheet) number

Integer

3

Priority

Integer

4

Selection

String

5

Custom field 1

String

6

Custom field 2

String

7

Custom field 3

String

8

Custom field 4

String

9

Custom field 5

String

10

Custom field 6

String

11

Custom field 7

String

12

Custom field 8

String

13

Custom field 9

String

14

Custom field 10

String

When setting a property that applies to all alarm types on the specified project tag (that is, if numAlarmType is -1), the property is identified by one of the following values:

Value

Property

Data Type

0

Alarms Enabled

Boolean

1

Remote Ack tag

String (tag name)

2

Translation Enabled

Boolean

3

Dead Band Value

Real

4

Off

String

5

On

String

6

Ack

String

7

Deviation Setpoint

String (tag name)

8

Deviation Dead Band

Real

For more information about all of these alarm properties, see Tag Properties.

strOrNumVal

The value to set to the specified property. The value must be of the appropriate data type.

Returned value

This function returns one of the following possible values:

Value

Description

-4

The specified project tag (strTagName) does not exist.

-3

Wrong parameter type or inconsistent value.

-2

Invalid number of parameters.

-1

The function TagsDBBeginEdit was not executed successfully before this function was called.

0

Function executed successfully.

Notes

The following restrictions apply to the execution of this function:

  • The function can be executed only on the project runtime server — it cannot be called by a Graphics Script, Screen Script, or Command animation running on a thin client;

  • The TagsDBBeginEdit function must have been executed previously, in order to lock the tags database for editing; and

  • The TagsDBEndEdit function must be executed when the editing is done, in order to release the tags database and resume normal runtime operations.

For more information about the Tags Database functions and examples of how to use them, see Using TagsDB functions to edit the tags database during run time.

Note: A specific alarm condition, as defined by the tag name and the alarm type (for example, the HiHi alarm on MyTag1), can be in only one alarm group at a time. Therefore, please remember that when you assign an alarm condition to an alarm group, it will be removed automatically from its previous group, if any.

Also, make sure that an alarm group with the correct group/worksheet number actually exists before you try to assign an alarm condition to it.