List of network ports used by this software

  • Last UpdatedOct 29, 2026
  • 3 minute read

This is a list of the various network ports that are used by the project runtime, its subordinate drivers and utilities, and other related programs.

Port

Feature or Protocol

20

FTP Server (Data)

21

FTP Server (Command)

80

Web Server (HTTP), unencrypted

102

Siemens SIMATIC S7 Protocol, for the SIETH and SITIA drivers

110

Post Office Protocol version 3 (POP3), for incoming mail

118

Microsoft SQL Server Services

135

Distributed Component Object Model (DCOM), for OPC DA and OPC HDA

161

Simple Network Management Protocol (SNMP)

162

Simple Network Management Protocol (SNMP) Trap

389

Lightweight Directory Access Protocol (LDAP), unencrypted

443

Web Server (HTTPS), encrypted using SSL

465

Simple Mail Transfer Protocol (SMTP), for encrypted outgoing mail

502

Modbus TCP/IP, for the ADPRO, MODSL, MOTCP, and SCHNE drivers

587

Simple Mail Transfer Protocol (SMTP), for encrypted or unencrypted outgoing mail

636

Lightweight Directory Access Protocol (LDAP), encrypted using SSL

1028

FTP Client (Command)

1029

FTP Client (Data)

1234

AVEVA Edge project runtime server (also known as Data Server or TCP/IP Server), unencrypted

Tip: You can change this port number in your project settings. For more information, see Communication tab.

1433

Microsoft SQL Server

1434

Microsoft SQL Server Dedicated Administrator Connection (DAC)

1521

Oracle

1526

Oracle

2030

Oracle

3000

Python Language Server port (WebSocket) - will try 3000, 3002, 3004, 3006

3306

MySQL (can be configured to use 3306–3309)

3872

Oracle Management Remote Agent

3997

Studio Database Gateway (StADOSvr.exe)

Tip: You can change this port number in the gateway settings, especially if you need to run multiple instances of the gateway. For more information, see Manually running Studio Database Gateway.Traffic on this port is protected only when Secure Channel is enabled.

4322

Remote Agent (CEServer.exe), RemoteAgent without Use TLS enabled

4323

RemoteAgent with Use TLS enabled

4448

Mobile Access Runtime (MobileAccessTask.exe)

5432

PostgreSQL

22350

Wibu CodeMeter, for the License Server feature

32565

AVEVA Historian (connection from Studio Database Gateway to the Historian server; the port can be changed in the Historian Configurator)

44818

Allen-Bradley CIP (default), for the ABCIP driver

47808

BACNet UDP (default), for the BACNE driver

48010

OPC UA Server (default)

Tip: You can change this port number in your project settings. For more information, see Configure the communication settings for OPC UA Server.

51234

AVEVA Edge project runtime server (such as Data Server or TCP/IP Server), encrypted via TLS/SSL

Tip: You can change this port number in your project settings. For more information, see Communication tab.

Notes

Depending on which features you use in your project, you might need to update your network's firewall settings in order to open the corresponding ports and allow the traffic to pass through. For example, if you develop your project to send email alerts, you need to open port 25 for SMTP.

Many of the port numbers listed above are only the defaults for those ports. You can change them, but if you do, you need to do so on both the server side and the client side, and then you also need to update the firewall settings. Keep in mind that the project runtime acts as the server in some cases and as the client in others, depending on the feature or protocol.

The communication drivers (for example, MOTCP, ABCIP, BACNE) included in the list above are only a few of the most commonly used drivers. For more information about the port used by a specific driver, see the documentation for that driver.

Studio Database Gateway sends an ICMP echo request (ping) to the AVEVA Historian server before it connects. If the ping is blocked, the connection fails. Allow ICMP echo from the gateway computer to the Historian server, together with the Historian port.