Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Edge HMI

Create a batch history

  • Last UpdatedOct 29, 2026
  • 4 minute read

AVEVA Edge provides powerful tools that enable the user to create and manage batch historical information. The user is able to create batches by using the following formats:

  • Proprietary: When using the proprietary format, each batch will be stored on a different historical file. The user can save historical data in both the normal historical file and batch files at the same time (see Trend Folder for more information about these files).

  • Database: The historical data used for the batch is saved in the same table as the normal historical data; an additional table called BatchHistory keeps registers with the information about the batches. The list below describes the fields on the BatchHistory table:

    Field Name

    Data Type

    Description

    Group_Number

    Integer

    Trend group number. This is the number of the worksheet that you are creating to specify the tags that will be stored on your batch history.

    Batch_Name

    String

    Name of the batch

    Start_Time

    TimeStamp

    Date and Time that the batch was started.

    End_Time

    TimeStamp

    Date and Time that the batch was finished

    Pri_Table

    String

    Reserved

    Sec_Table

    String

    Reserved

    Description

    String

    Batch description

    Deleted

    Boolean

    0: Batch has not been deleted

    1: Batch has been deleted

    Tip: You can customize the name of the table and the name of the columns created in the database by editing the <project name>.APP file, as follows:

    [Trend]

    DefaultName=NewName

    [TrendGroupPRI|SEC]

    BatchHistory=TableName

    For example:

    [TREND001PRI]

    BatchHistory=MyTableForPrimaryDB

    [TREND001SEC]

    BatchHistory=MyTableForSecondaryDB

    [Trend]

    Group_Number=Trend_Worksheet

    Batch_Name=Load_Number

Batch History Configuration

When you add a Trend worksheet (see Trend folder) and click the Advanced button, the following window will display:

Trend Advanced Settings dialog

In the Batch pane, you can configure the saving of the batch history:

  • Start/Stop (input): Enter the tag that will start/stop your batches. When the tag in this field is set to TRUE (different from 0), the project will either start saving data to your batch file (if you are using proprietary format), or add a new register to the BatchHistory table on your database, indicating that a batch has been started. Note that historical data will be saved according to the configuration in the fields Save Trigger and Save On Tag Change options on the Trend Worksheet.

  • Name (input): This field represents the batch name; its meaning depends on the format selected on the Trend Worksheet:

    • If you selected Proprietary in the Type field, the Name should comply with the format [Path]<FileName>, where:

      • Path: An optional field. If the path is not specified, the batch history file will be stored in the same path as the <project name>.app file.

      • FileName: Name of the batch history file.

    • If you selected Database in the Type field, the value in this field will be stored in the Batch_Name field of the BatchHistory table.

      This field accepts String expressions, for example C:\MyBatches\{MyTagWithName}{MyTagWithNumber}.hst

  • Delete (input): When the tag specified in this field changes its value, the batch will be deleted. With the Proprietary format, the batch history file will be removed. With the Database format, it will set the Delete field in the BatchHistory table to true, but the saved historical data will remain. The Trend object only sees batches that have the delete field set to 0 (zero).

  • Existent (output): The tag entered on this field will receive the value 1 if the batch specified in the Name field already exists; otherwise the tag will receive the value 0.

  • Description (output): This field is available only when using the Database format. When the tag in the Start/Stop field changes to TRUE, the register that is added to the BatchHistory table will display the string in this field. This field accepts String expressions.

  • Save data even if batch is not running: If this field is unchecked, the historical data will be saved only when the tag in the Start/Stop field is TRUE.

    Tip: The Batch Historical data can be displayed to the user in either Graphical or Table format. See Trend Folder or Grid Object to display information in these formats.

In the Disk Space Control area, you can control disk usage:

  • History Life Time (days) field: Specify how many days to keep the history file on the disk. After the specified period, the file will be automatically erased. Use this option only for files based on a date.

  • Compress After (days) field: Specify how many days to keep the trend history file (HST, *.hst) on the disk before compressing the file. After the specified period, the file will be automatically compressed. This creates an HSZ file ( *.hsz ) with the file name based on the date of the compression. Use this option only for files based on a date. This option is not available for Windows Embedded target systems.

    In order to convert a compressed trend history file back to a binary HST file, see Converting Compressed Trend History Files to Uncompressed Binary Trend History Files.

In the Bad Quality area, you can determine what value will actually be saved in the batch history when the tag quality is BAD:

Type

Description

Tag Value

The actual value of the project tag when the tag quality was BAD, plus the specified Offset (if any).

Min Value

The minimum historical value of the project tag, minus the specified Offset (if any).

Max Value

The maximum historical value of the project tag, plus the specified Offset (if any).

Value

The specified Value only.

NaN

Not a number.

Please note that when History Format is Database and Bad Quality is NaN, all of the database fields will be saved as Float type.

Also, if a Trend Control screen object is configured to use the history generated by this Trend worksheet, then NaN entries are counted as 0 for the purpose of calculating a trend's statistical average and deviation.

Note: The Bad Quality feature cannot be used in projects running on Windows Embedded target systems.

Finally, in the Disable All Data Saving box, type the name of a project tag. When the value of the tag is TRUE (non-zero) during runtime, all data saving is disabled for this worksheet. Other Trend worksheets are not affected.