AVEVA™ Batch Management

Automatic Shutdown Requirements

  • Last UpdatedJun 06, 2017
  • 1 minute read

The main requirements for automatic shutdown in a batch process are:

  • The Batch Server computer must be connected to an uninterruptable power supply (UPS), which maintains power to the server computer for a minimum of five minutes.

  • The server software must recognize external commands initiated from the UPS that allow it to shut down gracefully with no manual intervention.

  • On computer restart, either through power restoration or manually, the batch system must completely restart run-time operation with no manual intervention.