AVEVA Batch Management Server Roles and Communications
- Last UpdatedNov 03, 2021
- 1 minute read
AVEVA Batch Management Server roles are determined by the information contained in the local RedState file on each server.
Redundant AVEVA Batch Management Server operation is controlled by a redundancy manager service running on each server. The heartbeat is exchanged through the cross-over cable between the two servers. Each redundancy manager controls the other local Batch Management processes. When a failover event occurs, the associated process activity is controlled by the redundancy manager.
A system parameter in the environment called Redundancy TimeOut sets the switch-over delay. You can configure the value. It is specified in seconds.
In the event that a redundant AVEVA Batch Management Server has failed to detect the heartbeat of the other server, it waits for the configured time before initiating a failover.