Configure CP to Generate a Return-to-Normal Message for a SENDCONF Message

Configure CP to Generate a Return-to-Normal Message for a SENDCONF Message

  • Last UpdatedOct 30, 2024
  • 1 minute read

You must use the Integrated Control Configurator (ICC) to set the Station Block parameter CFGOPT of the Control Processor (CP) to 2. This configuration enables the CP to generate a return-to-normal message when a SENDCONF message has been acknowledged (when the sequence block is unsuspended).

Here are the permitted values:

CFGOPT

0 = No configuration

1 = Auto checkpoint

2 = RTN to normal

To Configure the CP

  1. From the FoxView process_eng or software_eng environment display, select the top menu item, Config, then select CIO_Config to invoke ICC.

  2. From the Compound Selection dialog box, select the CP station compound (for example, CP4001_STA) and click OK.

    The ICC main dialog box appears.

  3. From the Compounds list, select the CP station compound.

  4. From the Compound functions list, select View Blocks/ECBs in this compound.

    A new dialog box shows the block name list for the selected compound.

  5. Select the block name STATION.

  6. From Block/ECB Functions, select Edit all Block/ECB Parameters.

  7. Scroll through the parameter list and find CFGOPT. Select the parameter and type 2 for the value.

  8. Click Enter.

  9. Click Done.

  10. To close ICC, click Exit.