AVEVA™ InTouch HMI

Run ArchestrA scripts in embedded industrial graphics

Run ArchestrA scripts in embedded industrial graphics

  • Last UpdatedMar 10, 2025
  • 1 minute read

When you run a managed InTouch application in WindowViewer, any ArchestrA scripts associated with elements or symbol scripts themselves run as expected.

However, some scripts contained in symbols can run for a long time and stop you from interacting with other InTouch elements.

To prevent this, you can set a script time-out that is applicable for all scripts in the managed InTouch application. A script time out stops script execution and returns the control to the operator.

By default, scripts time out after 5 seconds.

Set the script time-out

  1. Open a managed InTouch application in WindowMaker.

  2. On the File menu, point to Configure, and then select WindowViewer. The WindowViewer configuration screen appears.

  3. Select the Managed Application tab.

    Managed application tab in WindowViewer configuration screen to modify script timeout

  4. In the Script timeout (msec) box, type a value in milliseconds.

  5. Select OK.