Enables or disables High condition events and alarms.
Category
Alarms
Usage
TagName.AlarmHiDisabled
Parameter
TagName
Any integer, real, indirect analog tag, or alarm group.
Remarks
When .AlarmHiDisabled is set to 1, all High condition events and alarms are ignored. They are not stored in alarm memory, nor are they written to disk. It is very important to re-enable events/alarms, whenever possible, to avoid data loss.
This is the opposite of the .AlarmHiEnabled dotfield.
Data Type
Discrete (read/write)
Valid Values
1 = Disable alarms
0 = Enable alarms (default)
Example
The following example enables High alarms of the Tag2 tag:
Tag2.AlarmHiDisabled=0;