Troubleshoot SuiteLink communication problems

  • Last UpdatedJul 26, 2024
  • 2 minute read

If you encounter SuiteLink communication:

  • Confirm that Microsoft TCP/IP is operational on the computer on which the InTouch HMI is installed.

  • Verify the computer node name is 15 characters or fewer.

  • Confirm that SuiteLink is running as a service on the computer on which the InTouch HMI is installed.

  • SuiteLink is automatically installed during the InTouch installation. The SuiteLink service starts automatically. If the SuiteLink service stops, you must start it again.

The table below shows the Suitelink connection behavior for a non-admin user (standard user) in different versions of System Platform and the corresponding troubleshooting steps.

Scenario

Until System Platform 2020 R2 SP1

System Platform 2023

Troubleshooting

SMS not configured, run WindowViewer

No Logger message

No Logger message

NA

SMS not configured, connect client to WindowViewer

Unsecure connection established to WindowViewer. Warning message in Logger.*

Connection fails.

Warning message in Logger.*

  • In the configurator, select the option to allow unsecure connection.

    Unsecure connection gets established, with the warning message in Logger.

  • Configure Secure Suitelink connection.

SMS configured, run WindowViewer

Connection fails.

Error message in Logger.**

Connection fails.

Error message in Logger.**

  • Run WindowViewer as service

  • Run WindowViewer in interactive mode with administrator privilege, or

  • Add the WindowViewer user to the "ArchestrAWebHosting" group.

SMS configured, connect client to WindowViewer

Unsecure connection established to WindowViewer. Warning message in Logger.*

Connection fails.

Warning message in Logger.*

  • In the configurator, select the option to allow unsecure connection.

    Unsecure connection gets established, with the warning message in Logger.

  • Configure Secure Suitelink connection

SMS is not configured, Secure Suitelink Connection (V3) not configured, and Unsecure Suitelink Connection (V2) as fallback disabled

  • Suitelink client connects to WindowViewer.

  • Web Client binds to InTouch tag.

  • Warning message in Logger.*

  • Suitelink client does not connect to WindowViewer.

  • Web Client does not bind to InTouch tag.

    Error message in Logger when WindowViewer is launched.**

  • In the Configurator, configure the SMS.

  • Configure Secure Suitelink connection.

  • Select the option to allow unsecure connection as fallback.

Warning message* - Warning WWSLS Non-Encrypted communication channel established from 127.0.0.1(VIEW). Secure this channel by installing System Management Server on both nodes and upgrading to the latest version of both client and server products

Error message** - Error WWSLS [Multi-Line Message] - Encrypted inbound SuiteLink connections are not possible in this configuration.