Control access to features at runtime

  • Last UpdatedJun 19, 2024
  • 2 minute read

If you right-click on the Alarm Viewer control during run time, a context-sensitive (shortcut) menu appears.

Context Sensitive Alarm Viewer

You can control which menu commands are shown in the shortcut menu.

Configure the shortcut menu

  1. Right-click the Alarm Viewer control, and then select Properties.

    The AlarmViewerCtrl Properties dialog box appears.

  2. In the General tab, select the Show Context Sensitive Menu check box.

  3. Select Configure Context Menus.

    The Context Sensitive Menus dialog box appears.

    Context Sensitive Menus Dialog

    This dialog box shows a hierarchical list of commands that can appear in an Alarm Viewer control shortcut menu.

  4. Configure the shortcut menu options. You must select at least one shortcut menu command.

    This command

    Allows the run-time user to

     Ack Selected

    Acknowledge selected alarms. If Ack Selected and Ack Others menu items are both unchecked, the Use Default Ack Comment check box and the text box are disabled.

     Ack Others

    Acknowledge alarms by other methods. The user can select which alarms to acknowledge. If Ack Others is selected, you must select at least one of the submenu items.

     Ack All

    Acknowledge all active alarms.

     Ack Visible

    Acknowledge visible alarms.

     Ack Selected Groups

    Acknowledge all alarms with the same group name as the selected group(s) and with the same provider name.

     Ack Selected Tags

    Acknowledge all alarms with the same group name as the selected tag(s) and with the same provider, group, and priority.

     Ack Selected Priorities

    Acknowledge all alarms with the same priority as the selected priority or priorities and with the same provider and group.

    Suppress Selected

    Suppress selected alarms.

    Suppress Others

    Suppress alarms by other methods shown in the shortcut menu.

    Suppress All

    Suppress all alarms.

    Suppress Visible

    Suppress all visible alarms.

    Suppress Selected Groups

    Suppress all alarms with the same group name as the selected group(s).

    Suppress Selected Tags

    Suppress all alarms with the same tagname as the selected tag(s).

    Suppress Selected Priorities

    Suppress all alarms with the same priority as the selected priority or priorities.

    Unsuppress All

    Unsuppress all suppressed alarms.

    Query Favorites

    Open the Alarm Query dialog box.

    Stats

    Open the Alarm Statistics dialog box.

    Suppression

    Open the Alarm Suppression dialog box.

    Freeze

    Toggle the freeze/unfreeze mode of the Alarm Viewer control.

    Requery

    Re-run the alarm query.

    Sort

    Open the Sort dialog box.

  5. Select OK.

  6. Select Row Selection to enable users to select a row from the Alarm Viewer control during run time.

  7. Select Use Extended Selection to enable users to select multiple alarm records simultaneously from the Alarm Viewer control using the SHIFT or CTRL keys.

  8. Select Apply.