Tag keyword attributes

  • Last UpdatedJul 02, 2024
  • 5 minute read

The following table lists all attributes associated with InTouch tag keywords. The table include columns that describe the type of data associated with each tag attribute and its default value.

These tag attributes can be specified in any order in your DBLoad import file as long as the accompanying tag data matches its corresponding attribute. For example, if you insert a :IODisc keyword in an Excel import file, then all I/O discrete tags’ engineering units must be placed in the same Excel column as the EngUnits attribute.

Attribute

Acceptable Value

Default Value

AccessName

InTouch Access Name assigned to tag

None

AlarmAckModel

Alarm acknowledgement model

Integer

0 = Condition

1 = Event Oriented

2 = Expanded Summary

0

AlarmComment

Alarm comment assigned to the tag

Text string

None

AlarmDevDeadband

Tag deviation alarm deadband

Real

None

AlarmPri

Alarm priority assigned to the tag

1 to 999

1

AlarmState

Tag alarm state

On, Off, or None

None

AlarmValueDeadband

Tag alarm deadband

Real

0

Comment

Comment assigned to the tag

Text string

None

Conversion

Tag value conversion

Linear or Square Root

Linear

Deadband

Value deadband assigned to the tag

Real

0

DevTarget

Tag deviation target value

Real

0

DSCAlarmDisable

Discrete alarms disabled or enabled

0 = Discrete alarm enabled

1 = Discrete alarm disabled

0

DSCAlarmInhibitor

Name of the tag used to inhibit a discrete alarm

None

EngUnits

Engineering units assigned to tag

Text string

None

EventLogged

Event logging enabled or disabled

Yes or On = Event logging enabled

No or Off = Event logging disabled

No

EventLogging

Tag event logging enabled or disabled

No or Off = Logging disabled

Yes or On = Logging enabled

No

EventLoggingPriority

Priority assigned to events

1 to 999, 0 = not logged

0

Group

Name of the alarm group in which the tag belongs

$System

HiAlarmDisable

High alarm disabled or enabled

0 = High alarm enabled

1 = High alarm disabled

0

HiAlarmInhibitor

Name of the tag used to inhibit High alarm

Any discrete or analog tag

None

HiAlarmPri

Priority assigned to High alarm

1 to 999

1

HiAlarmState

High alarm enabled or disabled

No or Off = Disabled

Yes or On = Enabled

No

HiAlarmValue

High alarm point assigned to tag

Real

0

HiHiAlarmDisable

HiHi alarm disabled or enabled

0 = HiHi alarm enabled

1 = HiHi alarm disabled

0

HiHiAlarmInhibitor

Name of the tag used to inhibit HiHi alarm

Any discrete or analog tag

None

HiHiAlarmPri

Priority assigned to HiHi alarm

1 to 999

1

HiHiAlarmState

HiHi alarm enabled or disabled

No or Off = Disabled

Yes or On = Enabled

No

HiHiAlarmValue

HiHi alarm point assigned to tag

Real

0

InitialDisc

Initial value assigned to discrete tag

0, Off, False, or No = Off

1, On, True, or Yes = On

0

InitialMessage

Initial tag message

Text string

None

InitialValue

Initial value assigned to the tag

Real

0

ItemName

Name of the item assigned to the tag

Text string

None

ItemUseTagname

Use Tagname as Item Name option enabled or disabled

No or False = Disabled

Yes or True = Enabled

No

LoAlarmDisable

Low alarm disabled or enabled

0 = Low alarm enabled

1 = Low alarm disabled

0

LoAlarmInhibitor

Name of the tag used to inhibit Low alarm

Any discrete or analog tag

None

LoAlarmPri

Priority assigned to Low alarm

1 to 999

1

LoAlarmState

Low alarm enabled or disabled

No or Off = Disabled

Yes or On = Enabled

No

LoAlarmValue

Low alarm point assigned to tag

Real

0

LogDeadband

Logging deadband assigned to the tag

Real

0

Logged

Tag value logging enabled or disabled

No or Off = Logging disabled

Yes or On = Logging enabled

No

LoLoAlarmDisable

LoLo alarm disabled or enabled

0 = LoLo alarm enabled

1 = LoLo alarm disabled

0

LoLoAlarmInhibitor

Name of the tag used to inhibit LoLo alarm

Any discrete or analog tag

None

LoLoAlarmPri

Priority assigned to LoLo alarm

1 to 999

1

LoLoAlarmState

LoLo alarm enabled or disabled

No or Off = Disabled

Yes or On = Enabled

No

LoLoAlarmValue

LoLo alarm point assigned to tag

Real

0

MajDevAlarmDisable

Major Deviation alarm disabled or enabled

0 = Major Deviation alarm enabled

1 = Major Deviation alarm disabled

0

MajDevAlarmInhibitor

Name of the tag used to inhibit Major Deviation alarm

Any discrete or analog tag

None

MajorDevAlarmPri

Priority assigned to Major Deviation alarm

1 to 999

1

MajorDevAlarmState

Major deviation alarm enabled or disabled

No or Off = Disabled

Yes or On = Enabled

No

MajorDevAlarmValue

Major deviation alarm percentage assigned to tag

Real

0

MaxEU

Maximum engineering units value assigned to the tag

Real

32767

MaxLength

Maximum message length

Real

131

MaxRaw

Maximum raw value assigned to tag

Real

32767

MaxValue

Maximum value assigned to the tag

Real

32767

MinDevAlarmDisable

Minor Deviation alarm disabled or enabled

0 = Minor Deviation alarm enabled

1 = Minor Deviation alarm disabled

0

MinDevAlarmInhibitor

Name of the tag used to inhibit Minor Deviation alarm

Any discrete or analog tag

None

MinEU

Minimum engineering units value assigned to the tag

Real

-32768

MinorDevAlarmPri

Priority assigned to Minor Deviation alarm

1 to 999

1

MinorDevAlarmState

Minor deviation alarm enabled or disabled

No or Off = Disabled

Yes or On = Enabled

No

MinorDevAlarmValue

Minor deviation alarm percentage assigned to tag

Real

0

MinRaw

Minimum raw value assigned to tag

Real

-32768

MinValue

Minimum value assigned to the tag

Real

-32768

OffMsg

Discrete tag Off message

Text string

None

OnMsg

Discrete tag On message

Text string

None

ReadOnly

Tag value read only or read/write

Yes = Read Only

No = Read/Write

No

RetentiveAlarmParameters

Tag Retentive Parameters enabled or disabled

No or Off = Disabled

Yes or On = Enabled

No

RetentiveValue

Tag Retentive Value enabled or disabled

0, Off, False, or No = Disabled

1, On, True, or Yes = Enabled

No

RocAlarmDisable

Rate of Change alarm disabled or enabled

0 = ROC alarm enabled

1 = ROC alarm disabled

0

RocAlarmInhibitor

Name of the tag used to inhibit Rate of Change alarm

Any discrete or analog tag

None

ROCAlarmPri

Priority assigned to Rate of Change alarm

1 to 999

1

ROCAlarmState

Rate of Change alarm enabled or disabled

No or Off = Disabled

Yes or On = Enabled

No

ROCAlarmValue

Change in tag value by percent

Real

0

ROCTimeBase

Measurement period to calculate rate of change

Sec, Min or Hr

Min

SymbolicName

Symbolic name assigned to input data blocks by the S7 Tag Creator product. Symbolic names are listed in the S7 Tag Creator Symbol Table.

None