Specify the alarm providers for hot backup
- Last UpdatedJul 19, 2024
- 1 minute read
You can specify any of the following alarm providers:
-
InTouch
When you specify InTouch as the alarm provider, the provider must be InTouch for both the primary node and the backup node. However, the alarm group of the backup node can be different from that of the primary node.
-
Galaxy
To specify a Galaxy or Galaxy_<GalaxyName> alarm provider, you must configure AppEngine redundancy in the IDE.
-
Galaxy_<GalaxyName>
The valid characters for GalaxyName are alphanumeric and special characters $, #, and _.
When specifying Galaxy_<GalaxyName>, the Galaxy name must be the same for both the primary and the backup node.
When you specify Galaxy or Galaxy_<GalaxyName> as the alarm provider, the provider of the backup node can be Galaxy or Galaxy_<GalaxyName>.
The alarm group of the backup node must be the same as that of primary node.
Note: The system does not support hot backup pairs for alarms generated from two different Galaxies.