Configure a UDT member as an I/O tag
- Last UpdatedApr 08, 2025
- 2 minute read
You can configure a UDT member as an I/O tag in the same manner as other InTouch I/O tags. In the Properties grid, configure the Type, Access name, and Item name fields to set the member as an I/O tag.
Example: configure a UDT member as an I/O tag
-
Create the access name “SIM” for the local Simulator server.

-
Activate the SIM server from the Operations Control Management Console (OCMC).

-
Select and configure the ExcitationVoltage example member.

-
Configure properties to make the member an I/O Tag. You can also override the Access name and/or Item name at the instance level.
-
Set Type to I/O Integer
-
Set Access name to SIM (you can select from the drop down list)
-
Set Item name to i01
-
-
Create a graphic and add an animation with the reference shown in the following illustration.

-
Embed the graphic you just created and view it in run time. The value should bind to the I/O reference.