Configure the InTouch OPC UA Server
- Last UpdatedMay 29, 2025
- 1 minute read
The InTouch OPC UA Server provides access from an OPC UA client to InTouch HMI data, without the need for a gateway, or other protocol translation mechanism.
-
Launch AVEVA InTouch HMI Application Manager.
-
On the Tools tab, select OPC UA Configuration.
The OPC UA Server dialog box appears.
-
The OPC UA server will be disabled by default. To configure the server, select Enable OPCUA.

-
Edit the Port Number. By default the port will be set to 48032.
Note: The port number is unique for a user and RDS session. Assign alternate port numbers for additional RDS sessions.
-
Security Configuration: It is strongly recommended that you enable this option, as this will encrypt the payloads across the connection. Note that the client must match this configuration.
-
The Client Access Rules options allow you to determine the type of access the client will have to InTouch data.
-
Select the Allow anonymous client connection (no username/password) checkbox to allow anonymous access.
-
Select the Allow authenticated InTouch Users to write to attributes, depending on their security role checkbox to allow only authenticated users.
-
-
Select OK.
-
After configuration, start the WindowViewer to launch the OPC UA Server. OPC UA clients can now access InTouch HMI data.