AVEVA™ InTouch HMI

​.AlarmValueCount dotfield

  • Last UpdatedJun 19, 2024
  • 1 minute read

Tracks the total number of active value alarms for a specified tag or alarm group.

Category

Alarms

Usage

TagName.AlarmValueCount

Parameter

TagName

Any integer, real, indirect analog tag, or alarm group.

Remarks

This includes the count of HiHi, High, Low, and LoLo alarms. It includes both acknowledged and unacknowledged alarms. For non-expanded summary alarm tags, this count will not exceed 1. However, the count may vary with alarm groups.

Data Types

Integer (read-only)

Valid Values

0 or any positive integer

Example

Tag1 is an analog tag configured for value alarms. AVC is also an analog tag, which gets the total number of all alarm values present in Tag1.

AVC = Tag1.AlarmValueCount;

See Also

.AlarmDevCount, .AlarmDevUnAckCount, .AlarmDscCount, .AlarmDscUnAckCount, .AlarmROCCount, .AlarmTotalCount, .AlarmValueUnAckCount, .AlarmROCUnAckCount, .AlarmUnAckCount