​.AckROC dotfield

  • Last UpdatedJun 19, 2024
  • 1 minute read

Acknowledges the rate-of-change alarm of a specified local tag or all rate-of-change alarms of a specified alarm group.

Usage

TagName.AckROC=1;

Parameter

TagName

Name assigned to the integer, real, or indirect analog tag or the name of an alarm group.

Remarks

Set this dotfield to a value of 1 to acknowledge any outstanding rate-of-change alarms associated with a specified tag or alarm group. When the specified tag is an alarm group, all unacknowledged rate-of-change alarms associated with the tags within the specified group are acknowledged. When the specified tag is of any type other than alarm group, only the unacknowledged rate-of-change alarm associated with that tag is acknowledged. Setting this dotfield to a value other than 1 has no meaning.

Data Type

Discrete (read/write)

Valid Values

1

Examples

The following statement acknowledges a rate-of-change alarm associated with a tag named Tag1.

Tag1.AckROC=1;

This next example acknowledges all unacknowledged rate-of-change alarms within the alarm group named PumpStation:

PumpStation.AckROC=1;

See Also

.Alarm, .AlarmROC, .Ack, .UnAck, .AckDev, .AckDSC, .AckValue, .AlarmAckModel