Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ InTouch HMI

​.AlarmROCUnAckCount Dotfield

  • Last UpdatedJun 19, 2024
  • 1 minute read

Tracks the total number of unacknowledged rate-of-change alarms for a specified analog tag or alarm group.

Category

Alarms

Usage

TagName.AlarmROCUnAckCount

Parameter

TagName

Any real tag, integer tag, indirect analog tag, or alarm group.

Data Types

Integer (read-only)

Valid Values

0 or any positive integer

Example

Tag1 is an analog tag configured for rate-of-change alarms. ARUC is also an analog tag, which gets the total number of unacknowledged rate-of-change alarms present in Tag1.

ARUC = Tag1.AlarmROCUnAckCount;

See Also

.AlarmDevCount, .AlarmDevUnAckCount, .AlarmDscCount, .AlarmDscUnAckCount, .AlarmValueCount, .AlarmTotalCount, .AlarmValueUnAckCount, .AlarmROCCount, .AlarmUnAckCount