.LoLimit dotfield
- Last UpdatedJun 19, 2024
- 1 minute read
Changes a tag’s Low alarm limit.
Category
Alarms
Usage
Tagname.LoLimit
Parameter
Tagname
Any integer, real, or indirect analog tag.
Remarks
If you want to continue to use the run-time value of this dotfield after an intentional or accidental shutdown of WindowViewer, select the Retentive Parameters option in the Tagname Dictionary.
Data Type
Analog (read/write)
Valid Values
Must be in value range configured for the specified tag.
Example
This statement decreases the Low alarm limit for the MyTag tag by a value of 10:
MyTag.LoLimit=MyTag.LoLimit - 10;
See Also
.Alarm, .AlarmValue, .Ack, .LoStatus, .LoSet, .AlarmDisabled, .AlarmEnabled, .AlarmLoDisabled, .AlarmLoEnabled, .AlarmLoInhibitor