Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ InTouch HMI

Create custom filters using filter favorites

  • Last UpdatedApr 09, 2025
  • 2 minute read

You can select which records are included in your query results. For example, you can select a filter by the date of a record or the state of the alarm. You can select multiple fields to limit or expand your query results.

If you do not define a custom filter, then a default filter that queries all records is used.

Create custom filters

  1. Right-click the Alarm Pareto control and then select Properties. The AlarmPareto Properties dialog box appears.

  2. Select the Query Filter tab.

    Query/Filter tab in AlarmPareto Properties dialog

  3. In the left pane, select filter fields and then select Add to include them in the filter, which is shown in the right pane. The filter fields are described in the following table:

    Field name

    Filters query by:

    Class

    Alarm class.

    Type

    Alarm type.

    Priority

    Alarm priority.

    Name

    Alarm name.

    GroupName

    Alarm group name.

    Provider

    Alarm provider.

    Limit

    Alarm limit. Values are alphanumeric.
    The comparisons of these values in the Query Filter are done as a string comparisons.

    Operator

    Operator.

    OperatorFullName

    Operator’s full name.

    OperatorNode

    Operator’s node name associated with the alarm.

    OperatorDomain

    Operator’s domain name associated with the alarm.

    Comment

    Alarm comment.

    User1

    Alarm user-defined numeric value 1.

    User2

    Alarm user-defined numeric value 2.

    User3

    Alarm user-defined string value.

    Duration

    Unacknowledgement and alarm duration. A Duration column set equal to zero does not produce records with a null value in the query.

  4. To remove a field from the filters pane, highlight the field you want to delete and select Delete. Deleting a filter cannot be undone. When a message appears, select Yes.

  5. Configure the criteria for each filter field. For more information, see Define the column filter criteria.

  6. Configure the operators and grouping for the filter. For more information, see Group alarm columns.

  7. Configure the filter favorites file.

    1. In the Filter Favorites File box, type the network path and file name or select the ellipse button to browse for the file.

    2. To edit the Filter Favorites file, select the Edit Favorites File button. The Filter Favorites window opens, allowing you to add, modify, or delete filters from your favorites file. When you are done, select OK to save your changes and close the window.

  8. Select Apply.

TitleResults for “How to create a CRG?”Also Available in