.QualitySubstatus Dotfield
- Last UpdatedNov 07, 2016
- 1 minute read
The .QualitySubstatus dotfield shows the quality sub-status of a data value provided by an I/O Server.
Category
Tag
Usage
Tag.QualitySubstatus
Parameter
Tag
Any discrete, integer, real, indirect analog, or message tag type.
Data Type
Integer (read-only).
Valid Values (SSSS) and (QQ)
Substatus (SSSS) for BAD quality (QQ=0).
0 = Non-specific
1 = Configuration error
2 = Not connected
3 = Device failure
4 = Sensor failure
5 = Last known value
6 = Communication failure
7 =Out of service
Substatus (SSSS) for UNCERTAIN quality (QQ=1).
0 = Non-specific
1 = Last usable value
4 = Sensor not accurate
5 = Engineering Units exceeded
6 = Sub-Normal
Substatus (SSSS) for GOOD quality (QQ=3).
0 = Non-specific
6 = Local override
See Also
.QualityStatus, .QualitySubStatus, .Quality