Understand alarm acknowledgement models
- Last UpdatedJun 19, 2024
- 1 minute read
The InTouch HMI supports three models of alarm acknowledgement:
-
For condition-oriented alarms, an acknowledgment counts against all entries into the alarmed state up to the time of the acknowledgment.
-
For expanded summary alarms, an acknowledgment is only for a particular transition, whether to an alarmed state, to a sub-state, or a return to normal. All transitions into different alarm sub-states must be acknowledged before the overall alarm is considered acknowledged.
-
For event-oriented alarms (as in OPC), an acknowledgment is accepted only if it refers to the most recent activation event.