.AlarmHiHiInhibitor dotfield
- Last UpdatedJun 19, 2024
- 1 minute read
Returns the name of the inhibitor tag assigned to a HiHi alarm condition.
Category
Alarms
Usage
TagName.AlarmHiHiInhibitor
Parameter
TagName
Any integer, real, indirect analog tag, or alarm group tag.
Remarks
Configured in WindowMaker. Cannot be changed during run time.
Data Types
Message (read-only)
Example
The .AlarmHiHiInhibitor dotfield is used by setting .Name to an Indirect tag that is equal to the value of the .AlarmHiHiInhibitor tag then manipulating the value of the Indirect tag. The following statement returns the name of the alarm inhibitor tag for a HiHi alarm limit (assuming SomeIndirectTag is an analog indirect tag):
SomeIndirectTag.Name = AlarmedTag.AlarmHiHiInhibitor;
The inhibition state of the alarmed tag can be controlled by setting the value of the indirect tag as follows:
SomeIndirectTag = 1;
Turns on inhibition
HiHi alarms are disabled for AlarmedTag
SomeIndirectTag = 0;
Turns off inhibition
HiHi alarms can be generated for AlarmedTag
See Also
.AlarmHiInhibitor, .AlarmLoInhibitor, .AlarmLoLoInhibitor