AVEVA™ InTouch HMI

​.AckDev dotfield

  • Last UpdatedJun 19, 2024
  • 1 minute read

Acknowledges the minor or major deviation alarms of a specified local tag or all deviation alarms of a specified alarm group.

Category

Alarm

Usage

TagName.AckDev=1;

Parameter

TagName

Any integer, real, indirect analog tag, or alarm group.

Remarks

Set this dotfield to a value of 1 to acknowledge any outstanding deviation alarms associated with the specified tag or alarm group. When the specified tag is an alarm group, all unacknowledged deviation alarms associated with the tags within the specified group are acknowledged. Setting this dotfield to a value other than 1 has no meaning.

Data Type

Discrete (read/write)

Valid Values

1

Example

The following statement acknowledges a deviation alarm associated with the Tag1 tag:

Tag1.AckDev=1;

This next example would be used to acknowledge all unacknowledged deviation alarms within the alarm group named PumpStation:

PumpStation.AckDev=1;

See Also

.Alarm, .AlarmDev, .Ack, .UnAck, .AckDSC, .AckROC, .AckValue, .AlarmAckModel