.UnAck dotfield
- Last UpdatedJun 19, 2024
- 1 minute read
Monitors or controls the alarm acknowledgment status of local alarms.
Category
Alarms
Usage
TagName.UnAck=0;
Parameter
TagName
Any discrete, integer, real, indirect discrete and analog tag, or alarm group.
Remarks
Set this dotfield to a value of 0 to acknowledge any outstanding alarms associated with the specified tag or alarm group. When the specified tag is an alarm group, all unacknowledged alarms associated with the tags within the specified group are acknowledged. When the specified tag is any other type, only the unacknowledged alarm associated with that tag is acknowledged. Setting this dotfield to a value other than 0 has no meaning.
Data Type
Discrete (read/reset) only
Valid Values
0
Example
The following statement acknowledges any alarm associated with the Tag1 tag.
Tag1.UnAck=0;
This statement acknowledges all unacknowledged alarms within the alarm group named PumpStation.
PumpStation.UnAck=0;
.UnAck has an inverse dotfield called .Ack. When an alarm has been acknowledged, the value of the .Ack dotfield is set to 1.
See Also
.Ack, Ack(), .Alarm, .AlarmAckModel