Configuration errors include the following:

Source

Description

Reason

Responding LMX

Invalid Object ID

Attempt to get or set an attribute from an ApplicationObject on a remote engine, but that remote ApplicationObject is currently undeployed while the remote engine is deployed.

Requesting NMX

Invalid Platform ID

Attempt to get or set an attribute from an ApplicationObject on a remote platform, but that remote platform is currently undeployed.

Requesting LMX

Invalid reference

Attempt to get or set an attribute from an ApplicationObject that is not yet configured in the system. A bad reference.

Responding NMX

Invalid Engine ID

Attempt to get or set an attribute from an ApplicationObject on a remote engine, but that remote engine is currently undeployed while the remote platform is deployed.