Define steps with always true or always false conditions

Define steps with always true or always false conditions

  • Last UpdatedJan 16, 2025
  • 2 minute read

You can configure a step so that its step condition or jump condition is always or is never true.

This can be done with the following two conditions:

"Always True" condition setting

Always True

The condition always evaluates to true.

"Always False" condition setting

Always False

The condition always evaluates to false.

Note: If both the Step condition and the Jump condition are configured as Always True, then the Step transition occurs since the Step takes precedence over the Jump.
On the other hand, if the Step condition and the Jump condition are configured as Always False, then the Sequencer remains in the active step until an Advance ExecutionStateCmd or an StepNumCmd or StepNameCmd is issued.

To configure a step or jump to always execute

  1. Select the Step Program tab. The Step Program panel appears.

  2. Locate the step for which you want to change the step condition or jump condition.

  3. Select the Condition cell or Jump Condition cell of that step and select Always True.

    Selecting the always true condition for the condition cell

To configure a step or jump to never execute

  1. Select the Step Program tab. The Step Program panel appears.

  2. Locate the step for which you want to change the step condition or jump condition.

  3. Select the Condition cell or Jump Condition cell of that step and select Always False.

    Selecting the always false condition for the condition cell (LIVE)