Configuration errors
- Last UpdatedJul 26, 2024
- 1 minute read
To resolve configuration errors, refer to the Telemetry Server User Guide for detailed information. The basic way to resolve an error is to make one or more of the following changes, as applicable:
-
Check that the <PointName> in the dynamic tag reference is valid to allow the point to be created in the Telemetry Server database.
-
Check that the <PointType> and address in the dynamic tag reference are valid for the protocol and correct for the particular outstation. For some point types, such as Modbus digital points, you must additional items, such as bit offset and bit count.
-
In DNP3, address refers to PointNumber.
-
In IEC 60870, address refers to IOA.
-
In Modbus, address refers to PointAddress
-
-
Check that the <OutstationFullName> in the dynamic tag reference exactly matches the name of the outstation in the Telemetry Server database and that this is the correct outstation. The name is case sensitive.
-
Rename, or delete, the object that has the same name in the group, or move the object to a different group.