Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Application Server

Configuration requirements

  • Last UpdatedJul 29, 2024
  • 1 minute read

Before deploying the Primary and Backup AppEngines, all configuration requirements must be met.

  • Each AppEngine must be assigned to a separate WinPlatform.

  • A valid redundancy message channel (RMC) must be configured for each WinPlatform.

  • To deploy the Primary and Backup together, select Include Redundant Partner in the Deploy dialog box. This option is not available when doing the following operations:

    • Cascade deploy from the Galaxy

    • Multiple object selection deploy

    • Deploying the WinPlatform that hosts the Primary or Backup AppEngine

The following table shows a matrix of allowed operations based on specific conditions.

Condition

Deploy both primary and backup objects

Cascade deploy allowed

Backup AppEngine's host WinPlatform configured for failover and deployed

Yes

Yes

Backup AppEngine in error state

Yes

Yes

Backup AppEngine's host WinPlatform not deployed

No

Yes

Backup AppEngine's host WinPlatform not configured for failover and deployed

Yes

Yes

Deploy from Galaxy node

No

Yes

Deploy from WinPlatform hosting Primary AppEngine

No

Yes

Multiple object selection deploy

No

No

Backup AppEngine's host WinPlatform not configured for failover and not deployed

No

Yes

Deploy from Backup AppEngine

Yes

Yes

Deploy from Primary AppEngine

Yes

Yes