Configuration requirements
- Last UpdatedJul 29, 2024
- 1 minute read
Before deploying the Primary and Backup AppEngines, all configuration requirements must be met.
-
Each AppEngine must be assigned to a separate WinPlatform.
-
A valid redundancy message channel (RMC) must be configured for each WinPlatform.
-
To deploy the Primary and Backup together, select Include Redundant Partner in the Deploy dialog box. This option is not available when doing the following operations:
-
Cascade deploy from the Galaxy
-
Multiple object selection deploy
-
Deploying the WinPlatform that hosts the Primary or Backup AppEngine
-
The following table shows a matrix of allowed operations based on specific conditions.
|
Condition |
Deploy both primary and backup objects |
Cascade deploy allowed |
|---|---|---|
|
Backup AppEngine's host WinPlatform configured for failover and deployed |
Yes |
Yes |
|
Backup AppEngine in error state |
Yes |
Yes |
|
Backup AppEngine's host WinPlatform not deployed |
No |
Yes |
|
Backup AppEngine's host WinPlatform not configured for failover and deployed |
Yes |
Yes |
|
Deploy from Galaxy node |
No |
Yes |
|
Deploy from WinPlatform hosting Primary AppEngine |
No |
Yes |
|
Multiple object selection deploy |
No |
No |
|
Backup AppEngine's host WinPlatform not configured for failover and not deployed |
No |
Yes |
|
Deploy from Backup AppEngine |
Yes |
Yes |
|
Deploy from Primary AppEngine |
Yes |
Yes |